Cummins/Onan OTECA Transfer Switch

The Cummins/Onan OTECA is a transfer switch.

0
Parts

Troubleshooting

6
CodeSymptomCauseRemedy
379 − OVER CURROutput OverloadOutput current is excessive. Charger control may be failing.Cycle through the Setup menus to try and clear the fault. If the fault returns, the charger control may have failed.
441 − LOW BATT VOLTLow Battery VoltageConnect the battery.
442 − HIGH BATT VOLTHigh Battery Voltage1. A 12V battery is connected but the charger is set for 24V charging. 2. Large load dump may have caused momentary voltage rise.
2331 − LOW AC VOLTLow Input VoltageAC input voltage is more than 10% below nominal rated voltage.
2358 − HIGH AC VOLTHigh Input VoltageAC input voltage is more than 10% above nominal rated voltage.
2263 − HIGH BATT TEMPBattery Temp above 55 degrees C1. Battery’s ambient temperature is too high. 2. Possible shorted cells within the battery is causing an excessive battery temperature increase.

Symptom → cause → remedy extracted from this unit’s service/owner documentation; verify against the official manual before servicing.