Troubleshooting
3| Symptom | Cause | Remedy |
|---|---|---|
| I/O Module Not Found | The system does not detect an I/O module at an expected address. | Check that the number of I/O modules installed matches the number expected by the setup program. Check that the I/O modules are connected and the address DIP switches are set correctly. Check the diagnostic LED to verify that the module is receiving power and communicating with the controller. |
| I/O Module Not Installed | The software detects an I/O module that is connected but not expected by the setup program. | Check that the number of I/O modules expected in the Setup Program matches the number of modules installed on the transfer switch. Check that the I/O module address DIP switches are set correctly. Check the diagnostic LED. |
| I/O Module Communications Lost | Communication to an I/O module that was previously installed and working is lost. | Check the I/O module connections and diagnostic LED. |
Symptom → cause → remedy extracted from this unit’s service/owner documentation; verify against the official manual before servicing.
About
Kohler Model S — transfer switch. Specifications and parts compiled from manufacturer documents.