HomeTransfer SwitchesKohler TS 870

Kohler TS 870 Transfer Switch

The Kohler TS 870 is a transfer switch.

0
Parts

Troubleshooting

3
SymptomCauseRemedy
SDM will not display any information while the TSC 80 controller is energized.LCD communication signal may need to be reinitialized. Remove jumper JP9 on the TSC 80 controller for 5 seconds and reinstall. A loose ribbon cable connection. Misalignment of TSC 80 pins and ribbon cable. Ribbon cable for 16-pin connector is backwards. Refer to Figure 2 for correct orientation.
SDM faceplate LEDs and/or pushbuttons are inoperative.A loose ribbon cable connection. Misalignment of TSC 80 pins and ribbon cable. Ribbon cable for 12-pin connector is backwards. Refer to Figure 2 for correct orientation.
Defective TSC 80 controller (verify TSC 80 is energized and is operating correctly—check for flashing SYS OK green LED on the TSC 80 printed circuit board).

Symptom → cause → remedy extracted from this unit’s service/owner documentation; verify against the official manual before servicing.

About

Kohler TS 870 — transfer switch. Specifications and parts compiled from manufacturer documents.

Find parts

Service & wear parts for the Kohler TS 870.

Browse parts catalog