HomeTransfer SwitchesKohler TSC 80

Kohler TSC 80 Transfer Switch

The Kohler TSC 80 is a transfer switch.

0
Parts

Troubleshooting

6
SymptomCauseRemedy
Will not retransfer to utility source upon restorationA test mode has been activated. Utility voltage is outside the preprogrammed limits (check utility source for adequate voltage). A loose control connection. Faulty limit switch contact in the ATS motor circuit. Defective ATS motor. Defective TSC 80/TSC 80e controller (verify output signals with circuit board-mounted diagnostic LEDs).
Will not transfer to generator source upon failure of utility sourceGenerator set not producing enough voltage/frequency or output circuit power switching device open. Warmup time delay function has not timed out (verify TSC 80/TSC 80e timer setting).
Transfer to generator source without a power failure in the utility sourceA loose control connection. Faulty limit switch contact in the ATS motor circuit. Defective ATS motor. Defective TSC 80/TSC 80e controller (verify output signals with circuit board-mounted diagnostic LEDs).
Generator does not start or stop when it shouldVerify remote engine control panel is set for automatic mode. Verify the FTS4 selector is not in the off, engine start, or test positions.
No time delay when there should beVerify time delay function setting of TSC 80/TSC 80e controller. Verify load bus voltage decay during transfer to enable neutral delay timer.
Power is not available at the load terminals but the utility or generator power switching device appears to be closed to a live sourceThe power switching device’s trip unit (service entrance type ATS) has tripped on a fault on the system. Correct the fault.

Symptom → cause → remedy extracted from this unit’s service/owner documentation; verify against the official manual before servicing.