HomeLight TowersMaxi Lite Ii ML II

Maxi Lite Ii ML II Light Tower

The Maxi Lite Ii ML II is a light tower.

0
Parts

Troubleshooting

2

Symptoms & remedies

SymptomCauseRemedy
If a reading of 120 volts +10% is not measured at each terminal, the main breaker is faulty and must be replaced.Replace the faulty main circuit breaker.
A reading of less than 62.0 Hertz indicates that the engine is not running with enough speed to create the necessary power to operate all of the lamps consistently.Slow engine speed may be caused by a number of factors: A. Incorrectly adjusted engine governor. B. Clogged or dirty air and/or/fuel filters. C. Dirty fuel. D. Worn or damaged engine.A. Adjust governor as shown on the following page ( Figure D.1/Pg 15 ) until a reading of 62.0 Hertz is indicated on the multimeter display. B. Replace filters if there are any questions as to their condition. C. Drain fuel tank and fuel system and replace with known clean fuel. Replace fuel filter before re-starting the engine. D. Contact your local Allmand parts and service team for further assistance.

Fault codes and symptom→remedy steps extracted from this unit’s service/owner documentation; verify against the official manual before servicing.